AVAGM22 & AVAGM23 - INSTANTANEOUS
VOLTAGE RELAYS
WITH OR WITHOUT ADJUSTABLE SETTINGS.
APPLICATION
Over Voltage or Under Voltage protection of
equipment adjustable settings.
DESCRIPTION
Measuring element is rectified AC unit and
it is provided with or without setting adjustable. Voltage
sensing element energizes an instantaneous unit which provides
the necessary output contacts.
VOLTAGE RATING 220V/110V AC, 50 Hz
SETTING (WHERE PROVIDED FOR)
Overvoltage 110 – 140% adjustable.
Undervoltage 40 – 80% adjustable.
THERMAL RATING
Overvoltage relay:- The relay will
withstanding continuously three times the setting
voltage on any setting.
Undervoltage relay:- The relay will
withstand continuously three times the pick-up
(resetting) voltage at any setting.
BURDEN
Overvoltage relay :- Maximum burden 0.9 VA at
nominal voltage.
Undervoltage relay :- Maximum burden 2.5 VA at
nominal voltage.
CONTACTS
Up to three pairs of contacts in any
combination of normally open or normally closed can be
provided.
OPERATION INDICATOR
Hand reset, mechanically operated indicator
can be provided, if required.
CASE 170W x 235H x 175D mm (150 x
220mm cutout)
|