Free Web Hosting Provider - Web Hosting - E-commerce - High Speed Internet - Free Web Page
Search the Web

LEADERS     IN

 

AVDG14 - INVERSE TIME VOLTAGE

NEUTRAL DISPLACEMENT RELAY

 

Earth fault protection (employing the principle of neutral displacement) of generators which are earthed through a neutral earthing transformer and where immunity to operation on third harmonic frequency is essential: Capacitor bank protection etc.

It is an induction disc relay with an adjustable inverse time – voltage characteristic.

 

VOLTAGE RATING 

110 Volts A.C. or 230 Volts A.C.
Auxiliary Supply : 110/230V AC, 110/30/24V DC

 

SETTING

5.4, 7.5, 12.5 and 20 volts, selected by means of taps on a plug – board.

 

CONTACTS

Up to Four contacts in any combination of normally open or normally closed in Hand or Self reset configuration with Hand reset flag indication.

 

CASE

170W x 235H x 175D mm (150 x 220mm cutout)

AVOMEC GROUP
2AB,Bright Apartments,
7,Bright Street,
Calcutta-700019.
INDIA.
Fax:091-33-2400268
Phone:091-33-2479811
091-33-2471904
E-Mail: avomec@vsnl.com

Web Services by Payal Infotech