ACCUM- 31/33 REVERSE POWER RELAY
An essential Relay when Generators are used
in synchronization with other Generators.
When two alternators are running in
parallel and if engine of any of the alternators develops
trouble then the other good alternator will force drive the
damaged engine by making the alternator of the damaged engine
run as a motor and thereby result in a severe damage to the
second engine.
These Relays provide a sensitive, accurate
and economical protection against motoring conditions in
diesel alternators and back pressure turbines.
SPECIAL FEATURES:-
This is an induction disc type relay with
inverse time characteristics. The inverse time characteristics
are specially suited for Diesel Generator set since they
provide :-
 |
Extremely fast tripping during severe
faults. |
 |
Prevents inadvertent tripping due to
short duration of minor motoring action caused by sudden
loss of load or due to maladjustment of throttle settings
of two engines. |
 |
It is extremely simple in
construction thereby making maintenance most easy. |
 |
It is immune to voltage surges normally
occurring in D.G. Sets. |
 |
It is type tested to IS-3231 |
 |
It is suitable to operate up to 50°
C Ambient temperature which some times do occur in engine
rooms. |
 |
Relays are provided with standard
230V AC auxilliary voltage rating and there is no need to
provide auxilliary D.C.supply unless required. |
MAXIMUM TORQUE ANGLE:
Develops maximum torque when the applied
voltage lags the applied current by 30°
. It can operate even at Extremely Low Power Factors Occurring
during severe faults.
SETTINGS & OPERATING TIME:
Normally 0-20% continuously adjustable is
provided. Timings obtained are in inverse time
characteristics.
BURDENS Current coil 1VA, Voltage
coil 10VA
CONFIGURATION ACCUM31 (single
element), ACCUM33 (three element)
CONTACTS
Up to 4 pairs of self/hand reset
contacts with flag in any combination.
CASE ACCUM31
– 170W x 235H x 175D mm (150 x 220mm cutout) ACCUM33 – 475W
x 265H x 176D mm (435 x 222mm cutout)
|