AVAX21, AVAX31 - TRIP CIRCUIT SUPERVISION
RELAY
Used for supervision of Trip Circuits of
circuit breakers.
This relay operates self reset alarm
contacts for failure of trip supply and open circuit of trip
coil or trip circuit wiring.
AVAX21 Monitors the trip circuit
only when the circuit breaker is closed (without
preclosing supervision).
AVAX31 Monitors the trip circuit
in both closed and open position of the circuit
breaker.
RATINGS 30, 50, 110 or 220V DC
LOOP RESISTANCE
Maximum permissible loop resistance in the
alarm supply circuit is as under :
30 Volts normal supply
200 ohms
other voltage
400 ohms.
OPERATING TIME
The time between failure of the trip
circuit and operation of alarm contacts is less than 0.4
seconds.
THERMAL RATING
The relay units will withstand 120% of
rated voltage continuously.
BURDEN
|
Voltage | 30V | 50V |
110V | 240V |
| Maximum Watts | Trip supply | 0.5 |
0.85 | 1.7 | 3.7 |
| Alarm supply | 2.4 | 3.33
| 6.0 | 12.8 |
CONTACTS
Up to Four contacts in any
combination of normally open or normally closed in Hand or
Self reset configuration with hand reset flag indicator.
CASE 125W x 155H x 145D mm (116 x 145mm
cutout)
|